HATDDCBF48IA001
Details
Details
Copper Averaging Duct Temp Transmitter, 6 ft, 4-20mA, 32 to 95 deg F, 1/3 DIN RTD, LCD in deg F
Needs 15-30 VDC or 12-28 VAC power.
Key Features
- Output: 4-20mA, 2 or 3 wire
- Sensor accuracy: +/-0.18 deg F
Product Specifications
| Manufacturer | Greystone |
|---|---|
| Model | HATDDCBF48IA001 |
| Sensor | 1000 ohm platinum RTD, 2 wire, IEC 751, 385 alpha, thin film, 1/3 DIN |
| Sensor accuracy | +/-0.18 deg F (+/-0.1 deg C) at 32 deg F (0 deg C) |
| Probe sensing range | -4 to 140 deg F (-20 to 60 deg C) |
| Probe | Soft copper, 0.312 in. (7.94 mm) diameter, multiple RTDs |
| Averaging length | 6 ft (1800 mm) |
| Wire material | FT-6 rated plenum cable, 22 AWG |
| Output | 4-20mA, 2 or 3 wire |
| Output configuration | Factory configured |
| Scaled range | 32 to 95 deg F (0 to 35 deg C) |
| Transmitter accuracy | +/-0.2% of span, including linearity |
| Power supply | 15-30 VDC or 12-28 VAC |
| Consumption (max) | 20 mA |
| Protection circuitry | Reverse voltage protected and output limited |
| Output drive at 24 VDC | 700 ohm max |
| Display | 3-digit LCD, deg F (factory configured) |
| Display range | 3 digit, -88.8 to 888 as required |
| Display size | 1.5 x 0.65 in. (38.1 x 16.5 mm) |
| Digit height | 0.45 in. (11.4 mm) plus deg C/F symbol |
| Ambient operating range | 32 to 122 deg F (0 to 50 deg C), 0 to 95% RH |
| Enclosure | Grey polycarbonate UL94-V0, IP65 (NEMA 4X), hinged and gasketed cover |
| Enclosure dimensions | 4.43 x 4.58 x 2.11 in. (112.5 x 116.5 x 53.7 mm) |
| Wiring connections | Screw terminal block, 14 to 22 AWG |
| Country of origin | Canada |